Investor Presentaiton slide image

Investor Presentaiton

NRA, Japan Nuclear Regulation Authority Appendix Fire Safety Research on HEAF: High Energy Arcing Fault ■ At Onagawa-1, fire took place due to short circuit inside MC during the 2011 Tohoku Earthquake. ■ High energy gas generated by arcing fire was propagated to the other cabinets through the control cable duct. ■ In 2012, JNES started HEAF tests at U.S. KEMA and S/NRA/R continues them. HEAF simulation Test at KEMA in U.S. 28 No. 8 cabinet Source: Tohoku Electric Power, May 2011, http://www.nsr.go.jp/archive/nisa/earthquake/files/hou koku230530-2.pdf ■Currently, S/NRA/R is actively participating in the OECD/NEA international joint projects, PRISME-2 and HEAF. ■The acquired data have been used for developing the Review Guides for Fire Protection and Fire Hazard Analysis for the new regulatory requirements.