Scientific Method Example - Seal Leak Potential cause Poor installation by one fitter Poor installation by all fitters Overpressure Generic seal problem Component problem BAKERRISK Verification Review of maintenance history where similar work carried out Review of maintenance procedures with all fitters concerned Review of DCS data Background gas level measurements Review spares stock against manufacturer's specification · Finding Leaks have occurred where other fitters have installed seal Hypothesis FALSE No evidence that the work was being done differently to that in FALSE the manual No evidence of overpressure Slight rise in average toxic gas levels for past 18 months (not acted upon) Spares supplier changed 2 years previously. Same spec but slight difference in compressibility of O-ring seal Hazards 29 | CCPS Incident Investigation Book 3rd Edition | 23 May 2019 | 16:25-16:50 FALSE CONFIRMED CONFIRMED 24 24